What is the meaning of ASC scaling for the setting of Analogue output of ATS48 Soft Starter.
Refer to attached document; there is a formula for AO assignment.
For motor current, please see below: ---
Is = 20ma * [X(%) /ASC].
Where “X” represents the percentage reading compared to the nominal value selected (motor nominal current, nominal torque ...).
Example:
AO (Analog Output) => OCr : Motor current
O4 (Configuration of the type of signal supplied by output AO) => -020:0-20mA signal
ASC range is from 50 to 500% and factory setting is 200.
And for Example: if you program In = 120A as per Motor detail then X will be equal to 100% if 120A read by ATS48 [means=>120 A monitored by Motor Current (LCr) parameter from displayed menu (SUP)].
So, if ASC = 200%.
Then AO will be :=> 20ma * [X(%) /ASC].
=> 20mA *[100/200] = 10 mA
For motor current, please see below: ---
Is = 20ma * [X(%) /ASC].
Where “X” represents the percentage reading compared to the nominal value selected (motor nominal current, nominal torque ...).
Example:
AO (Analog Output) => OCr : Motor current
O4 (Configuration of the type of signal supplied by output AO) => -020:0-20mA signal
ASC range is from 50 to 500% and factory setting is 200.
And for Example: if you program In = 120A as per Motor detail then X will be equal to 100% if 120A read by ATS48 [means=>120 A monitored by Motor Current (LCr) parameter from displayed menu (SUP)].
So, if ASC = 200%.
Then AO will be :=> 20ma * [X(%) /ASC].
=> 20mA *[100/200] = 10 mA
Released for: Schneider Electric India


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.