How to configure node address of TM171EP14R expansion.
Expansion module TM171EP14R node address is the position of Dip switch + Addr_CAN_OB.
The default value of Addr_CAN_OB is 1. To locate Addr_CAN_OB refer the following steps:
- Open the Somachine HVAC - Device
- Navigate to Expansion Module in Project tree on the left side of computer screen.
- Click on CAN On Board option in BIOS parameters
- Enter the appropriate value for require node address in Addr_CAN_OB.
For Example:
To put in extension module address "8" and dip switch 1 and 2 are turned off then you need to set Addr_CAN_OB to 8 and if 1 and 2 dip switch are turned on then you need to set Addr_CAN_OB to 5.
Refer the attached guide and snapshot for more details.
The default value of Addr_CAN_OB is 1. To locate Addr_CAN_OB refer the following steps:
- Open the Somachine HVAC - Device
- Navigate to Expansion Module in Project tree on the left side of computer screen.
- Click on CAN On Board option in BIOS parameters
- Enter the appropriate value for require node address in Addr_CAN_OB.
For Example:
To put in extension module address "8" and dip switch 1 and 2 are turned off then you need to set Addr_CAN_OB to 8 and if 1 and 2 dip switch are turned on then you need to set Addr_CAN_OB to 5.
Refer the attached guide and snapshot for more details.
Released for: Schneider Electric India
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.