How can we help you today?

Altivar Process SEMI F47 settings.

The design and dimensioning of the circuit makes Altivar Process Series drives possible to continue the operation in the limits that are stated in specification SEMI F47-0706 after setting of following parameters:

> Set "IPL" parameter to "NO" the phase loss function is de-activated.
> Adjust "uSL" parameter versus main supply value
> Adjust "uST" to upto 3s
> Set "STP" parameter to "MMS" DC bus maintained.

Refer the attached Manufacturer Declaration.

Schneider Electric India

Attachment(s)
ATV Process - Manufacturer Statement for SemiF47.zip [939.38 KB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Contact support - +1800-103-0011
  • Price List
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings