The design and dimensioning of the circuit makes Altivar Process Series drives possible to continue the operation in the limits that are stated in specification SEMI F47-0706 after setting of following parameters:
> Set "IPL" parameter to "NO" the phase loss function is de-activated.
> Adjust "uSL" parameter versus main supply value
> Adjust "uST" to upto 3s
> Set "STP" parameter to "MMS" DC bus maintained.
Refer the attached Manufacturer Declaration.