{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
M340 Read_Var or Write_Var function block freeze in case slave not response.
Check the Timeout setting in GEST parameter of read_var EF. If it is not set then assign the timeout value.
Timeout is a multiple of 100ms means if 30 is setted as timeout then it will be 30*100ms =3sec. Reduce it if want a fast response considered that the slave device should be get replied in this time frame.
If the communications timeout is left at the default value of zero (0). A timeout value of zero 0) will cause the function block to never timeout.

This results in the The READ_VAR and WRITE_VAR block to never close the TCP/IP connection. To resolve the issue, define a timeout value in  the '%MW+2' management word of the READ_VAR or WRITE_VAR block.

Schneider Electric India

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: