How can we help you today?

Is NBU able to evacuate energy when ATV71 drive is connected to Generator.

NBU (network braking unit) is able to evacuate energy if some equipment on grid is able to consume this energy, else line voltage increase and drive and NBU have no way to brake. So, if you use NBU on generator, then voltage will increase (maybe up to damage the generator) and drive will be no longer able to brake.

Schneider Electric India

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.