{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Is NBU able to evacuate energy when ATV71 drive is connected to Generator.
NBU (network braking unit) is able to evacuate energy if some equipment on grid is able to consume this energy, else line voltage increase and drive and NBU have no way to brake. So, if you use NBU on generator, then voltage will increase (maybe up to damage the generator) and drive will be no longer able to brake.

Schneider Electric India

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: