{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Describe M251 TCP server behaviour and keep alive
In M251 it is not possible to enable or disable the Keep alive feature on the default SoMachine modbus TCP server.
The M251 TCP Server have the following behaviour when the Client does not close the socket correctly or not keep alive message was received:

The following behaviour is the same when the PLC is in RUN or in STOP state.

1. Default configuration:
The socket will be closed after 35 seconds.
2. Using a ModbusTCP Slave Device
The socket will be closed after the configured TimeOut ( only the socket opened by the configured Master)

M251

Schneider Electric India

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: