How can we help you today?

What is the reason that BMENOC03X1 IO Scanner stops scanning some servers with Bad Health status if the server device is Power Cycled.

This issue is related to the firmware and same has been corrected with Firmware version 2.14 or higher.
The resolution addresses issue where some IO Scanning lines stop scanning with bad health status if the server device is power cycled when communicating thru a router.  Code changes were implemented to prevent corrupted events in tasks from occurring when the server device was power cycled.
Firmware v 2.14 is attached.
For higher version visit SE Website i.e. www.se.com

Schneider Electric India

Attachment(s)

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.