How can we help you today?

What is INF29 on ATV980.

INF29 is MCE Power brick internal error.
It is due to Interrupted communication between the CMP6 (Power board) and the CMI1 (Inverter
brick) and CPLD internal communication interruption.

If the drive has the failure randomly than it may be an issue with the control wire.  Via SoMove service Section, they can indicate which wire (Connections) is impacted, and then they need to change this particular wire.
In most of the case, the wire is not fixed (not in a good position inside the plug)

it is recommended to change the power board and one Inverter board (the one which is detected by somove- service section) mostly the inverter board on the brick is impacted.

Schneider Electric India

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.