How can we help you today?

How to program ATV12 for Sink/Source operation.

The Logic inputs type nPL parameter page 51 (of the programming manual given in below link) is used to adapt the operation of the logic inputs to the technology of the programmable
controller outputs.

https://www.se.com/in/en/download/document/BBV28581/

• Set the parameter to POS for Source operation.
• Set the parameter to nEG for internal Sink operation.
• Set the parameter to EnEG for external Sink operation.
Note: The modification will be taken into account only at the next control power-on.

Schneider Electric India

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.