How to do RS-485 connection in Vamp57 relays.

6* RS-485 tem RS-485 interface termination resistor for “-“ connection
5* RS-485 - RS-485 interface “-“ connection
4* RS-485 + RS-485 interface “+“ connection
3* RS-485 tem RS-485 interface termination resistor for “+” connection
2 RS-485 G RS-485 interface ground terminal
1 RS-485 SHD RS-485 interface cable shield connection

NOTE! *Interconnect 3 & 4 and 5 & 6 when termination is needed.

refer vamp57 RS485 connection.jpg

Schneider Electric India

Attachment(s)
vamp57 RS485 connection.JPG.jpg [64.34 KB]