How to remove the LED Alarm in MiCOM Px3x
After the reboot of the device, the ALARM LED is ‘on’ due to a deliberate distortion of the parameter checksum which initializes the desired cold restart automatically.
Please read out the corresponding entries in the monitoring signal memory
(‘MiCOM Px3x / Operation / Operating data rec. / MT_RC / Mon. signal record.’):
Use the right arrow button to read all the entries.
In order to switch off the ALARM LED please clear the monitoring signal memory
(‘MiCOM Px3x / Operation / Control and Testing / MT_RC / Reset recording’):
Oper/CrtlTest/MT_RC
Reset recording
2
Please enter the input mode, change the value to ‘execute’:
Oper/CrtlTest/MT_RC
Reset recording
2
Execute
and press the ENTER key. The number of entries in the monitoring signal memory will be ‘0’ now and the ALARM LED will go ‘off’:
Oper/CrtlTest/MT_RC
Reset recording
0
Please read out the corresponding entries in the monitoring signal memory
(‘MiCOM Px3x / Operation / Operating data rec. / MT_RC / Mon. signal record.’):
Use the right arrow button to read all the entries.
In order to switch off the ALARM LED please clear the monitoring signal memory
(‘MiCOM Px3x / Operation / Control and Testing / MT_RC / Reset recording’):
Oper/CrtlTest/MT_RC
Reset recording
2
Please enter the input mode, change the value to ‘execute’:
Oper/CrtlTest/MT_RC
Reset recording
2
Execute
and press the ENTER key. The number of entries in the monitoring signal memory will be ‘0’ now and the ALARM LED will go ‘off’:
Oper/CrtlTest/MT_RC
Reset recording
0
Released for: Schneider Electric India
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.