Customer would like to monitor CB operations through IEC61850 in MiCOM P143
In Micom P14x series , we only have CB operations parameter over IEC61850 & it is available in XCBR logical node;  " OpCnt.stVal - CB Operations "
Refer to the latest IEC61850 documents from the link : https://www.se.com/in/en/product-range-download/60765-micom-p14x/
ID => FA377167_en
Title => What are the logical nodes for Breaker control in MiCOM Px3x or Px4x
URL => https://www.se.com/in/en/faqs/FA377167