What type of GSM/GPRS service are required for the FactoryCast Gateways (TSXETG302x) SIM card?

Issue:

Identify what type of GSM/GPRS cellular service is required for SIM cards used with FactoryCast Gateways TSXETG302x for reliable remote access and routing.

Product Line:

TSXETG3021

TSXETG3022

Environment:

FactoryCast HMI Gateway deployed over GSM/GPRS (2G) using a carrier SIM for remote monitoring/control and Modbus/Ethernet routing services.

Cause:

Cellular carriers offer M2M (Machine‑to‑Machine)-oriented GSM/GPRS subscriptions that differ by:

  • Data plan sizing (billing by MB/month).
  • IP addressing (Static vs Dynamic).
  • Inbound TCP port policy (some plans block ports—often <1024—for security). If inbound ports are blocked, remote connections to the gateway can be constrained.
  • Regional availability note: TSXETG302x relies on 2G (GSM/GPRS). Many operators have sunset plans or have already retired 2G/3G, varying by country and carrier—verify coverage where you deploy.

Resolution:

Choose an M2M GSM/GPRS subscription that supports the gateway’s remote access needs:

  1. Public APN + Public IP: Prefer plans that provide a public APN with a public, Internet‑reachable IP for the SIM.
  2. Static IP: Use a static IP to simplify fixed inbound access, firewall rules, and diagnostics.
  3. No inbound TCP blocks: Select plans where incoming TCP ports are not blocked, so routing services on the TSXETG302x are fully usable.
  4. Size the data plan: Match the plan’s monthly data allowance to your expected traffic.
  5. Confirm 2G support: Before ordering SIMs, confirm local 2G (GSM/GPRS) is still active with your target MNO(s); if sunset is imminent, consider alternate connectivity paths.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
  • 환경설정 센터