How to Log the Modem Interaction for an Internal Modem on an ION Meter

Issue
How to log Modem interactions

Product Line
ION8600
ION7300
ION8500
ION8400
ION8300
ION7550/ION7650
ION8800
ION7500/ION7600

Environment
Hyper Terminal

Cause
To troubleshoot internal ION Modems, complete the following procedure then analyze the different strings.

Resolution
Make two connections to the meter: COM1 via RS232/485 and the modem via RJ11

  1. Switch COM1 protocol to Modemgate
  2. Open a HyperTerminal session to COM1
  3. To see the typed text and responses, select File > Properties > ASCII Setup > and check the 'Echo typed characters locally' box > click OK

    Hyper Terminal
  4. Log the entire connection (Transfer> Capture Text)
  5. Power cycle the meter. In HyperTerminal there will be some init strings with some OK responses, wait until it is done
  6. Type ati0 (to get the modem type)
  7. Type at&v (to get the current settings)
  8. Dial into the meter via modem. In HyperTerminal you should see RING, then hear a bunch of squawking (the modem establishing a connection) if there is a speaker. At this stage do not press any keys; it will list the negotiation parameters.
  9. Disconnect the site. You should see a disconnect message in HyperTerminal
  10. Ensure the LED lights on the side of the meter go out. If they don't type ath0

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings