브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to Interpret Integer Registers on the PowerLogic Energy Meter; Multiplier Table for Calculating Actual Values

The raw data from an integer register read will not give the user a complete real-world value. A multiplier must be applied to the Integer register value to complete the information. The multiplier used to calculate the actual real-world value varies depending on the register being read and the CT size.
As stated in the register listing for the Energy Meter:
"For measured data, the float format registers are recommended. The Integer format registers can be difficult to use for the measured data, as a multiplier must be used for each one to get the correct value. Most of the multipliers change depending on the CT Size. Reading the float format registers avoids the need to use multipliers."

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings