Goals and Symptoms
How to wire a 2 phase 5 wire system, on an ION 7600 Series meter
Causes and Fixes
Va1a2= 240V
Vb1b2=240V
Va1b1= 170V
Va1b2=170V
Va2b1= 170V
Va2b2=170V
Wiring and Configuration
- Use 2 PTs and 2 CTs
- VOLTS MODE = 4W-Wye
Leave V3 unconnected
________________________________________