Loading settings onto a VAMP relay that doesn't have the same complete part number.

Issue

Can the settings file from a VPG210‑001361 relay be directly loaded into a VAMP 210‑5A7ADA‑3.20 relay using VAMPset?

Product

VAMP relays

Environment

VAMPset configuration software
VAMP 200‑series and 210‑series relays
Settings file compatibility
Part number and firmware validation

Cause

VAMP relays rely on their complete part number and firmware version to determine feature sets, hardware options, and supported configuration parameters. Differences in part numbers or firmware versions make setting files incompatible and may lead to functional mismatch or errors.

Resolution

A settings file cannot be loaded into a VAMP relay if the complete part numbers do not match exactly. Each relay with a different part number must be manually configured to ensure proper operation.

Additionally, even if the part numbers match, the settings file cannot be loaded if the firmware versions are different. In such cases, settings must be recreated manually or the firmware must be aligned before attempting to load the file.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings