브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Why am I getting an error: "The Main Drive or Secondary Drive is full. Runtime cannot execute" on the Magelis when installing with a USB stick?
Issue:
"The Main Drive or Secondary Drive is full.  Runtime cannot execute" appears on the Magelis when trying to install an application.

Product Line:
XBTGC/GH/GK/GT, HMIGTO/STO/STU

Resolution:
This error message can appear when the Magelis does not have a CF card/SD card installed.  To confirm, goto the Data Locations in Vijeo Designer and check if you have "User Application", "Data Files / Forms", "Recipes", or "Web Server" set for Secondary Drive.  If yes, then this means that you need to have a CF/SD card (depending on unit) installed in the unit.  Once you add a CF/SD card, reloading from the USB stick complete successfully. Alternatively, you may set the data locations to use Main drive if you do not have a secondary or optional drive.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings