브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
EGX300 with firmware 4.450 not plotting demand properly
Issue
EGX300 with firmware 4.450 does not plot demand properly on the gateway site.  It shows demand as negative values at times.

Product Line
EGX300

Environment
EGX site
EGX disk image

Cause
The EGX300 is incorrectly calculating demand as cumulative data i.e. it tries to calculate interval data by subtracting the last data record with the current data record.  This incorrect calculation causes some demand values to drop to negative numbers if the previous interval's demand is higher than the current one.

Resolution
*Warning: The firmware utilities listed here can cause permanent damage to your product if applied incorrectly. Before downloading any firmware updates, verify the firmware you are downloading is appropriate for the specific model number of your product. If you have any doubts, contact Technical Support for guidance.*

*Warning: Devices should be disconnected from all monitoring software before performing a firmware upgrade*


This has been corrected in the latest EGX300 firmware update. Update the EGX300 firmware and apply the disk update attached below.

NOTE: FA212757 describes how to upgrade the firmware via command prompt using FTP

슈나이더 일렉트릭 Korea

첨부 파일
egx04461.bin [2.57 MB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings