How to configure the PowerChute Network Shutdown Parameters on a Network Management Card?

Article available in these languages:

  • 스페인어
  • , 프랑스어

Issue:
How to configure the PowerChute Network Shutdown Parameters on a Network Management Card?

Product:
PowerChute Network Shutdown version 4.4.x and 5.x

Environment:
All supported OS

Cause:
Informational

Solution:
The Username and authentication phrase entered in the PowerChute Parameters must match those entered in the PowerChute web UI setup. To view the PowerChute Parameters on the Network Management Card (NMC), log into the card and go to Configuration and Shutdown; at the bottom of the page, you will see the PowerChute Parameters.

For assistance with the PowerChute Username, Password, and Authentication Phrase requirements see Schneider Electric What are the PowerChute Network Shutdown Username, Password, and Authentication Phrase requirements.

NMC menu options
PowerChute Shutdown Parameters
If HTTPS or HTTP is not enabled, you must enable the one you will use for communication in the PowerChute Parameters to allow a connection. If HTTP or HTTPS are not enabled, you will see the error Cannot connect to https://ip address:443 or HTTP://ip address 80.
Error registering with network card
Note: HTTP is disabled by default on the Network Management Card. When viewing the PowerChute Parameters, the option to enable HTTP is grayed out. To utilize HTTP, you must first enable HTTP web access and then enable HTTP access within the PowerChute Parameters, as shown above.
NMC Configure > Network > Web> Access MenuNMC web access settings page

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings