Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
What are the assignments for the output relays on an ATV212 ?

Article available in these languages: Тайский

Issue:
ATV212 output relays assignments.

Product Line:
ATV212

Environment:
Output relays

Cause:
n/a

Resolution:
FLA, FLB, FLC are the terminals for a single pole, double throw (Form C) relay and the default assignment is ``inversion of fault relay``.  Off = drive faulted, On = no drive fault.  Parameter F132 can be used to change this relay function.

RYA, RYC are terminals for a single normally open contact (Form A) and the default setting is ``speed attained``.  The relay contact closes when the hertz value assigned to F100 is reached.  F100 is defaulted to 0.  A common customer request is for ``drive running``.  Parameter F130 can be assigned to 14 for ``drive running``.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings