Video: ATV312 - How to use logic inputs for up and down speeds.
Issue:
How can I program the drive to use logic inputs to speed up and down the motor?
Product line:
Altivar 312
Environment:
All models, all serial numbers
Resolution:
Program the following parameters
Under CTL menu:
LAC= L2 or L3 (hold for 3 seconds) Access Level
Under FUN menu, UPD-
rFC= Fr2 Ref. 2 switching
USP= LI3 (+) speed assign.
dSP= LI4 (-) speed assign.
Fr2= Updt Reference 2 Channel
When LI3 is activated, the motor will speed up.
When LI4 is activated, the motor will slow down.