Is the remote graphic keypad display, VW3A1101, compatible with the ATV312 drive?
Issue:
Can you use VW3A1101 with ATV312 drive?

Product Line:
ATV312

Environment:
All models

Cause:
Display

Resolution:
Yes, the VW3A1101 keypad is compatible with the ATV312 drive.  The keypad must have minimum CPU V1.2IE09.

It is not direct connected to the drive.  At minimum, an adaptor and a cable are required:
VW3A1105 is a female-female adaptor between cable and keypad
VW3A1104R10 is a 1meter cable
VW3A1104R30 is a 3meter cable
VW3A1104R50 is a 5meter cable
VW3A1104R100 is a 10meter cable

An optional remote mount kit, VW3A1102, will include the VW3A1105 adaptor.
An optional door, VW3A1103, adds to the remote mount kit to increase IP54 rating to IP65.