What is the communications cable between the 984 Compact A120 PLC to a Magelis XBTRT511?
Issue
What is the communications cable between the 984 Compact A120 PLC to a Magelis XBTRT511?
Product Line
Compact 984, Magelis XBTRT511, Vijeo Designer Lite
Resolution
If the Compact 984 PLC has a RJ45 comm port, use the XBTZ9711 + XBTZG939.
If the Compact 984 PLC has a DB9 comm port, use the XBTZ9710 + XBTZG939 adapter.
The Compact PLC series 258/265/275/285 have a RJ45 comm port. All others Compact have a DB9 comm port.
What is the communications cable between the 984 Compact A120 PLC to a Magelis XBTRT511?
Product Line
Compact 984, Magelis XBTRT511, Vijeo Designer Lite
Resolution
If the Compact 984 PLC has a RJ45 comm port, use the XBTZ9711 + XBTZG939.
If the Compact 984 PLC has a DB9 comm port, use the XBTZ9710 + XBTZG939 adapter.
The Compact PLC series 258/265/275/285 have a RJ45 comm port. All others Compact have a DB9 comm port.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.