Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
How to Configure PowerSCADA Operation to Run as a Service
Issue
Downtime in the event of a system reboot.

Product Line
PowerSCADA Operation (PSE) 8.x

Environment
Runtime

Cause
For applications that provide runtime and historical data to clients, a service interruption cannot be tolerated.  The application should start automatically at system power on to minimize downtime.

Resolution
When PSE is installed, the service 'Citect Runtime Manager' is created.  This service adds the functionality to start the project automatically after the server is restarted.  Follow these two steps to configure this service:

1.  Add a dependency to FlexNet Licensing Service.  Open a command prompt (DOS window) and type this command to run:
sc config "Citect Runtime Manager" depend= "FlexNet Licensing Service"

2.  Change the startup type to 'Automatic (Delayed Start)' and start the Citect Runtime Manager service.


Now the user can log in and log out without disrupting the system.  For complete information refer to System Development Guide for PSE 8.1.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings