PM810 Energy Summary Usage and Energy Per Shift Usage Modbus Register read a value of 0
Title
PM810 Energy Summary Usage and Energy Per Shift Usage Modbus Registers Return 0
Language
English
Issue
Energy Summary Usage and Energy Per Shift Usage Modbus registers return a value of 0 when read from a PM810 meter.
Product Line
PM800
PM810
PM820
PM850
PM870
Note: PM810 is a legacy, reduced‑feature device. Energy Summary Usage and Energy Per Shift Usage are not supported on this model.
Environment
Modbus communications
Energy data acquisition
Cause
The PM810 does not support Energy Summary Usage or Energy Per Shift Usage calculations.
Although the Modbus register list shows the Float registers (11864 to 11958) as supported, these values are derived from MOD10 registers (16202 to 16346) that are not implemented on the PM810. As a result, the derived Float registers do not return valid data.
Resolution
Energy Summary Usage and Energy Per Shift Usage are not supported on the PM810.
When these Modbus registers are read on a PM810 meter, they will return a value of 0. This is expected behavior and cannot be corrected through configuration or firmware changes.
If Energy Summary Usage or Energy Per Shift Usage values are required, use one of the following meters that support this capability:
- PM820
- PM850
- PM870
Опубликовано для: Schneider Electric Казахстан
Вложения
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.