Issue:
Wondering if you need to uncouple the motor before running an autotune?
Product Line:
All Altivar products
Environment:
All part numbers
Cause:
Some Drive manufacturers rotate the motor during the autotune test so they require the motor to be disconnected from the load.
Resolution:
No. The Autotune function used on Schneider Electric Drives does not turn the motor so it is not necessary to uncouple the motor from the load.
You should be sure to enter all of the motor nameplate data correctly, and only perform an Autotune on a motor that has not been running.
An autotune on a warm motor will provide incorrect results, and may impact speed and torque performance.
An Autotune may not always be required for all applications, but if the correct motor information has been entered and the motor has not been running, the performance (speed and torque regulation) of the system will be improved.
Automatic Autotune may not be a good choice for most applications, and this function should only be used if directed.
Wondering if you need to uncouple the motor before running an autotune?
Product Line:
All Altivar products
Environment:
All part numbers
Cause:
Some Drive manufacturers rotate the motor during the autotune test so they require the motor to be disconnected from the load.
Resolution:
No. The Autotune function used on Schneider Electric Drives does not turn the motor so it is not necessary to uncouple the motor from the load.
You should be sure to enter all of the motor nameplate data correctly, and only perform an Autotune on a motor that has not been running.
An autotune on a warm motor will provide incorrect results, and may impact speed and torque performance.
An Autotune may not always be required for all applications, but if the correct motor information has been entered and the motor has not been running, the performance (speed and torque regulation) of the system will be improved.
Automatic Autotune may not be a good choice for most applications, and this function should only be used if directed.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.