PSO Notification Settings and Notification History popup does not open
Where
Product Line
Power SCADA Operation 9.x
Environment
Power SCADA Operation 9.x
Cause
Known issue with PSO 9.0 CU2. Will be fixed in CU3
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
IMPORTANT: Solution is only applicable to Cumulative Update 2, do not apply if you are not updated to this version.
Find & Edit the "PLSNotification.ci" inside your PLS_Inlcudes project. Preferably using your Cicode Editor from your PSO Studio IDE.
Use the "Find Function" feature to find the following function:
```
LaunchNotificationSettings()
```
Inside this function there is a method/ subroutine called
```
DllClassCallMethod(m_oNotificationServiceInstance, "LaunchSettings", sDataPath, sIPs, sUserName, sLanguage);
```
Comment out the "sLangauge" argument & Re-terminate the statement. Like this.
```
DllClassCallMethod(m_oNotificationServiceInstance, "LaunchSettings", sDataPath, sIPs, sUserName);//, sLanguage);
```
Do the same for this FUNCTION:
LaunchNotificationHistory(STRING sFilter, STRING sClusterName = "")
Replace
```
DllClassCallMethod(m_oNotificationServiceInstance, "LaunchResults", sDataPath, sIPs, sClusterName, sFilter, sLanguage);
```
With
```
DllClassCallMethod(m_oNotificationServiceInstance, "LaunchResults", sDataPath, sIPs, sClusterName, sFilter);//, sLanguage);
```
Save the LaunchNotificationSettings function.
Update Pages in citect gfx builder.
Always "Pack" databases on your projects
Recompile your project. Remember to perform a full recompile, not an incremental one.
Always run "Computer Setup Wizard".
Run your project.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.