Is it possible to monitor the Ethernet Port Status of an HMIST6 in EcoStruxure Operator Terminal Expert

Issue:
Looking for an internal system variable that will reveal the status of the Ethernet port of an HMIST6

Product Line:
Harmony HMI, HMIST6, HMISTM6, EcoStruxure Operator Terminal Expert

Resolution:
Currently in EcoStruxure Operator Terminal Expert V3.2 SP1, there is no way to determine the status of the Ethernet port by the means of a built-in  Internal System Variable.

As a workaround, we could monitor the Quality property of an External Variable. Here are the different states that the Quality property could be in:

ValueDescription
0, 4

Access to device address and device address value is normal.

1, 3, 5, 7

Cannot access the device address.

8, 12

Device address value is invalid.

9, 13, 15

You cannot access the device address. Also, the device address value can be invalid.

2, 6, 10, 11, 14

Not in use



Here is an example script that will write the Quality property to a variable named "StatusVar". Note Var1 is our external variable.

blockly

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings