undefined undefined
{}

Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
Чем мы можем помочь сегодня?
Do the TM3AI2H, TM3AI4, TM3AI8 or TM3TI4 modules require an external loop power supply or do the modules provide it for the 4-20mA current loops ?
The TM3AI2H, TM3AI4, TM3AI8 or TM3TI4 require an external loop power supply for their 4-20mA current loops. The module does not provide it.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие: