Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
How to access a Bit in a WORD variable in EcoStruxure Operator Terminal Expert?

Issue:

Alternative to access directly a bit of a WORD, without creating a BOOL type variable pointing to this specific bit.

Product:

EcoStruxure Operator Terminal Expert v3.x , v4.x (EOTE)

Environment:

HMI Configuration Software in Windows

Resolution:

Option 1: Define a BOOL variable that points to a specific bit of a WORD.

1

Note: This requires creating a new variable for each bit you need.

Option 2: Use a custom script to automatically create multiple variables. If adapted, the same script can be reused for several variables.

Part of the script:

2

Result:

3

Attached Resources:

  • EOTE Project: Minimum version v3.5 required to open.
  • Control Expert Project: Minimum version v15.1 required.
  • Video: Demonstrates the final result.

Schneider Electric Казахстан

Вложения
FAQ000279923.zip [18.02 MB]
Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings