Issue
To inform users the incorrect IO scanner device control block bit map in Modicon Quantum with Unity Ethernet Network Modules User Manual.
Product Line
Modicon Quantum
Environment
140NOE77101
Resolution​​​​​
Effected Documentation: Modicon Quantum with Unity Ethernet Network Modules User Manual
Related Product part number: 140NOE77101/11
· To use %MDx.4 as device control block, the double word to enable/disable each I/O scanner entry is described below:
Register | |||||||||
Double Word %MDx[0] | Table Entry # | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Bit | 31 | 30 | 29 | 28 | 27 | 26 | 25 | 24 | |
Table Entry # | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | |
Bit | 23 | 22 | 21 | 20 | 19 | 18 | 17 | 16 | |
Double Word %MDx[1] | Table Entry # | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 |
Bit | 15 ** | 14 ** | 13 ** | 12 ** | 11 ** | 10 ** | 9 ** | 8 ** | |
Table Entry # | 25 | 26 | 27 | 28 | 29 | 30 | 31 | 32 | |
Bit | 7 ** | 6 ** | 5 ** | 4 ** | 3 ** | 2 ** | 1 ** | 0 ** | |
Table Entry # | 33 | 34 | 35 | 36 | 37 | 38 | 39 | 40 | |
Bit | 31 | 30 | 29 | 28 | 27 | 26 | 25 | 24 | |
Table Entry # | 41 | 41 | 43 | 44 | 45 | 46 | 47 | 48 | |
Bit | 23 | 22 | 21 | 20 | 19 | 18 | 17 | 16 | |
Table Entry 49 through 112 | |||||||||
Double Word %MDx[4] | Table Entry # | 113 | 114 | 115 | 116 | 117 | 118 | 119 | 120 |
Bit | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | |
Table Entry # | 121 | 122 | 123 | 124 | 125 | 126 | 127 | 128 | |
Bit | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
-
- NOTE**: it is the bit of MDx[1] used for I/O scanner table entry 17 to 32, not MDx[0].
Bit number: Bit 0 is a low bit counting from right side.
Example:
If users configure %MD1:4 as device control block, %MD1[0] bit 31 can enable/disenable I/O scanner table entry 1. %MD1[1] bit 15 can enable/disenable I/O scanner table entry 17.
- NOTE**: it is the bit of MDx[1] used for I/O scanner table entry 17 to 32, not MDx[0].
Register | |||||||||
%MWx+1 | Table Entry # | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Bit | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | |
Table Entry # | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | |
Bit | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | |
%MWx+2 | Table Entry # | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 |
Bit | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | |
Table Entry # | 25 | 26 | 27 | 28 | 29 | 30 | 31 | 32 | |
Bit | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | |
%MWx+3 | Table Entry # | 33 | 34 | 35 | 36 | 37 | 38 | 39 | 40 |
Bit | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | |
Table Entry # | 41 | 41 | 43 | 44 | 45 | 46 | 47 | 48 | |
Bit | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | |
Table Entry 49 through 112 | |||||||||
%MWx+8 | Table Entry # | 113 | 114 | 115 | 116 | 117 | 118 | 119 | 120 |
Bit | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | |
Table Entry # | 121 | 122 | 123 | 124 | 125 | 126 | 127 | 128 | |
Bit | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
-
Bit number: Bit 0 is a low bit counting from right side.
Example:
If users configure %MD1:4 as device control block, %MW2 bit 15 can enable/disenable I/O scanner table entry 1. %MW3 bit 15 can enable/disenable I/O scanner table entry 17.
Schneider will correct the documentation -- Modicon Quantum with Unity Ethernet Network Modules User Manual to match the current implementation.