Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Bienvenido(a) al sitio web para México de Schneider Electric

Te damos la bienvenida a nuestro sitio web para México.
		
¿Cómo podemos ayudarte hoy?
Is a LAL36400MB with a short handle required instead of a LAL36400 as the main breaker in a 400a NQ or NQOD panel?

Issue:
Is a LAL36400MB with a short handle required instead of a LAL36400 as the main breaker in a 400a NQ or NQOD panel?

Product Line:
NQ and NQOD Panelboard

Environment:
Products sold in North America

Resolution:
No, either could work. The door on the trim will close when the handle on LAL36400 is in the on or off position. If the breaker trips with the door shut the handle might slightly push on the door when the free-to-trip mech works but that shouldn`t cause any real problem.

Schneider Electric Mexico

Explora más
Rango:
Explora más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Sustitución y reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Obtén un presupuesto
  • Dónde comprar
  • Empleo
  • Perfil corporativo
  • Informar una conducta indebida
  • Accesibilidad
  • Sala de redacción
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Términos y condiciones
  • Change your cookie settings