Issue:
How do you switch speed control from terminals to the remote keypad on an ATV12?
Product Line:
ATV12
Environment:
All Models and serial numbers
Cause:
None
Resolution:
Programming:
Notes: Function control will be the terminals start and stop via logic input LI1, and remote speed pot speed control if LI4 is low. If you turn on LI4, the remote HMI or keypad will have full control over the drive.
How do you switch speed control from terminals to the remote keypad on an ATV12?
Product Line:
ATV12
Environment:
All Models and serial numbers
Cause:
None
Resolution:
Programming:
- Using the knob push enter, scroll down to Conf and push enter
- Now scroll down to CtL menu and push enter
- Select Fr1 and push enter, set to AI1 for speed pot and push enter
- Scroll down to CHCF and push enter, set to SEP and push enter
- Scroll down to CD1 and push enter, set to ter and push enter.
- Scroll down to FLO and set to LI4, assuming you are using LI4 as the switch between remote HMI control and Terminal control and push enter
- Scroll down to FLOC and set this to LCC (remote keypad) and push enter
Notes: Function control will be the terminals start and stop via logic input LI1, and remote speed pot speed control if LI4 is low. If you turn on LI4, the remote HMI or keypad will have full control over the drive.
Publicado para: Schneider Electric Mexico


¿Necesitas ayuda?
Selector de productos
Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.
Pedir presupuesto
Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.
Centro de ayuda
Encuentra recursos de soporte para todas tus necesidades en un solo lugar.