Will VR breakers interrupt 5 amps and below chop current?
Issue:
Will VR breakers interrupt 5 amps and below chop current?

Product Line:
Metal Clad

Environment:
Application

Cause:
Can disregard SPD protection

Resolution:
The average chop current for copper-chromium contacts used in VR breakers is about 3 to 3.5 amps and the maximum is about 5 amps"