With only 3 logic/digital inputs, can you use 2 preset speeds with the S-Flex Altivar 212?

Issue:
With only F, R and RES terminals, can you use 2-preset speeds with the S-Flex Altivar 212?

Product Line:
Altivar Machines, Altivar 212, S-Flex

Environment:
All models and serial numbers

Cause:
Wiring / Programming

Resolution:
This can be accomplished by programming VIA to function as a Logic input, as follows:
Press Mode to AUF (Quick Menu) Enter, scroll down and set LL (Low Limit) to your 1st preset
Mode back to AUF - scroll down to F - - - (Extended Menu) and press Enter
F109 = 2 (assigns VIA as a logic input)
F118 = 6 (assigns the preset speed function to VIA)
Mode back to AUF, scroll down to
SR1.. Enter and set to your desired High/Preset Speed
Close a contact between P24 and VIA to run at high/preset speed, open that contact to run at the LL - Low Speed setting

Schneider Electric Mexico

Explora más
Rango:
Explora más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Sustitución y reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Obtén un presupuesto
  • Dónde comprar
  • Comunidad Schneider Electric
  • Empleo
  • Perfil corporativo
  • Informar una conducta indebida
  • Accesibilidad
  • Sala de redacción
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Términos y condiciones
  • Change your cookie settings