Why does the HDPM6000 have duplicate Modbus registers listed

Issue:

Why does the HDPM6000 have duplicate Modbus registers listed

Product Line:

HDPM6000

Environment:

HDPM6000 Modbus Register Map

Cause:

The Modbus Register list provides two Modbus registers with the same alarm register with two different Modbus register addresses.

For example: 10220 Warning and 10820/10830 Warning what is the difference for these two alarm registers?

Resolution

Some registers are legacy and only support up to 120 circuits.  (i.e. 10220)

The new registers now support the new features of the HDPM6000 and a total of 192 Circuits. (i.e. 10820, 10830)

HDPM6000 Protocol and Modbus Guide: PowerLogic™ HDPM6000 Protocol Guide | Schneider Electric