Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Bienvenido(a) al sitio web para México de Schneider Electric

Te damos la bienvenida a nuestro sitio web para México.
		
¿Cómo podemos ayudarte hoy?
Could the FH breaker achieve series rating with fast acting fuse the same as with 9999CLM?

Issue:

Legacy FH breaker series rating with fast-acting fuse

Product Line:

Legacy Circuit Breaker

Environment:

Products sold in the United States.

Cause:

Product features.

Resolution:

Series ratings are highly specific. You can't substitute something in a series rating and assume it achieves the same. Series ratings exist because those specific combinations were tested in front of UL and approved to assume that rating. Substitutes void that series rating.

As per Seneca: We cannot state the same rating can be achieved using fast-acting fuses because that specific combination has not been tested.

Schneider Electric Mexico

Explora más
Rango:
Explora más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Sustitución y reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Obtén un presupuesto
  • Dónde comprar
  • Comunidad Schneider Electric
  • Empleo
  • Perfil corporativo
  • Informar una conducta indebida
  • Accesibilidad
  • Sala de redacción
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Términos y condiciones
  • Change your cookie settings