What is a bPF fault on the ATS22 soft starter?
Issue:
bPF fault on the ATS22.
Product Line:
Altistart ATS22
Environment:
All
Cause:
Bypass contactor detected fault
Resolution:
Check for a welded bypass contactor or shorted SCR.
If you find a shorted SCR or bypass contactor, you will need to replace the soft starter.
Reference the ATS22 installation guide (BBV51330)