How to set up a fault reset function on ATV630 Process drive?

Article available in these languages: Japanese

Issue:
Fault reset function on the ATV630

Product Line:
Altivar ATV630

Environment:
All Process drives

Cause:
Fault reset function needed

Resolution:
Go into Menu 5 complete settings and enter
Go down to submenu 5.11 Error/Warning Handing and enter
Go to Fault Reset and Enter.
Go to Fault Reset Assignment
Choose digital input desired to act as a fault reset.