{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
What causes OFS to give a Polling rate overrun message?
Polling Rate Overrun is when OFS is requesting too much data and the PLC is not able to respond in a timely manner.  The Minimum Update Rate could be increased to give the PLC more time to respond.

-Locate the file named 'OFSinternal.xml' and make a backup copy of it. It should be in the following path: C:\ProgramData\Schneider Electric\OFS\3.60.0.0\
-Open the file named 'OFSinternal.xml' using 'Wordpad.
-Change the view to 'Word wrap to ruler'.
-Change the value of the "MinUpdateRate" value="1000".
-Save the changes.

NOTE:  The path above is for OFS v3.6 but it will also work for v3.5 but the path will be different.

Schneider Electric Malaysia

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: