Issue:
ATV630 set up the run command on DI1.
Product Line:
ATV630
Environment:
2-wire control
Cause:
n/a
Resolution:
Suggest to go to menu 5.5 and set 2-wire control to 2-wire and set 2-wire type to Level. This will automatically assign DI1 to run forward.
ATV630 set up the run command on DI1.
Product Line:
ATV630
Environment:
2-wire control
Cause:
n/a
Resolution:
Suggest to go to menu 5.5 and set 2-wire control to 2-wire and set 2-wire type to Level. This will automatically assign DI1 to run forward.
Released for: Schneider Electric Malaysia




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.