Issue:
ATV630 and ATV930 showing brF or brake feedback fault.
Product Line:
ATV630 or ATV930 drives
Environment:
All
Cause:
The monitoring of the brake (assign the braking contact to a logic input) does not
match the braking command.
Resolution:
brake feedback and the control circuit.
• Check the mechanical state of the brake.
• Check parameter BCI → brake contact input
• Check parameter BLC → brake assignment.
• Check parameter BRT → brake release time.
• Check parameter BET → brake engage time.
ATV630 and ATV930 showing brF or brake feedback fault.
Product Line:
ATV630 or ATV930 drives
Environment:
All
Cause:
The monitoring of the brake (assign the braking contact to a logic input) does not
match the braking command.
Resolution:
brake feedback and the control circuit.
• Check the mechanical state of the brake.
• Check parameter BCI → brake contact input
• Check parameter BLC → brake assignment.
• Check parameter BRT → brake release time.
• Check parameter BET → brake engage time.
Released for: Schneider Electric Malaysia




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.