Issue:
Is the integrated display active when ModBus Network is attached to ATS48 or ATS22.
Product Line :
Altistart Soft Starters
Environment:
Open style Soft Starters
Cause:
Communication
Resolution:
The ATS48 and ATS22 soft starters have a built in display as part of the soft starter. The RJ-45 port can be used for a remote mounted display keypad or for Modbus network. If the RJ-45 port is used for communications or for remote keypad the local display on the soft starter control board will still operate.
The single available port cannotbe used for both a remote keypad and for Modbus communication unless you add a port expander which allows for 2 Modbus Network Masters. Schneider Electric does not offer and expander, so this would require a 3rd party product. Another option is to monitor the motor using a TeSys T.
Is the integrated display active when ModBus Network is attached to ATS48 or ATS22.
Product Line :
Altistart Soft Starters
Environment:
Open style Soft Starters
Cause:
Communication
Resolution:
The ATS48 and ATS22 soft starters have a built in display as part of the soft starter. The RJ-45 port can be used for a remote mounted display keypad or for Modbus network. If the RJ-45 port is used for communications or for remote keypad the local display on the soft starter control board will still operate.
The single available port cannotbe used for both a remote keypad and for Modbus communication unless you add a port expander which allows for 2 Modbus Network Masters. Schneider Electric does not offer and expander, so this would require a 3rd party product. Another option is to monitor the motor using a TeSys T.
Released for: Schneider Electric New Zealand




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.