{"searchBar":{"inputPlaceholder":"Search by keyword or ask a question","searchBtn":"Search","error":"Please enter a keyword to search"}}
{}

Welcome to the Schneider Electric Website

Welcome to our website.

Select your location

Welcome the the Schneider Electric French website. It looks like you are located in the United States, would you like to change your location?

Traduisez en francais
{"support":{"yesButton":"yes","noButton":"no","feedback":{"title":"What can we do to improve?"},"submitButton":"Submit","successMessage":"Thank you for your feedback","title":"Was this helpful?","feedbackPercentLabel":"of people found this helpful","captcha":{"error":"Please tick the box"}}}
Search FAQs

How to write to the coils of a Quantum PLC using a WRITE_VAR

Issue
How to write to the coils of a Quantum PLC using a WRITE_VAR

Product Line
PL7 and UNITY

Environment  
Windows 7, Windows 10

Resolution
The following example demonstrates how to use a WRITE_VAR to write to the coils of a Modicon
Qunatum PLC, using an '140NOE771xx' Ethernet module.

WRITE_VAR(ADR#{3.120}4.0.1,'%M',22,4,%MW920:1,%MW925:4)

Writes coil 000023 through 000026 in a Quantum PLC that is configured for Modbus address 20.

Expression (3.120) instructs the WRITE_VAR to send the command out of XWAY address 3.120.
A value of 100 is added to the Modbus address for defining the XWAY address to a Modbus device.
The XWAY address must also be defined in the 'Connection Configuration' table of the Premium
Ethernet module device port configuration.

Expression 4.0.1 invokes the WRITE_VAR command to send the data out of
'Module 4', 'Channel 0', 'Sender address Ad0=1' in the Premium PLC. For a Modicon
device, the Sender address Ad0 is alsways equal to 1.

Expression '%M',22,4 will write four bits to coil 000023 through coil 0000026 in the Quantum PLC. The
reason for the offset is because Premium starts of with internal bit %M0 and the Quantum starts with
coil 000001.

Expression %MW920:1 is used for the starting word of the 'Transfer Table' with a length of 1 word. The
bit structure is reversed for the transfer table. (i.e., word 920 is represented as 2#0000 0000 0000 1111
in the PL7 animation table for the four bits written in the above instruction.

Expression %MW925:4 is the starting word for the 'Management Word' table with a length of 4 words.

Explore more

Can't find what you are looking for?

Reach out to our customer care team if you have any questions or need more technical support.
Explore more