Do the GV7 and the LR9F trip on phase loss?
Please note - both the GV7 and LR9F ranges are no longer available, this FAQ is for reference only

Yes they do, though their trip time for "unbalanced phases" is much faster than that of the conventional thermal magnetic overloads, such as GV2/3 series or LRD series.

The GV7 and LR9F series will both trip after 4 seconds (+ or - 20%) on phase loss where an LRD or GV2/3 can keep running for up to 2 hours unless an overload is detected in the remaining phases.

Schneider Electric New Zealand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings