Is the undervoltage trip included with time delay units for Powerpact breakers?
Issue:
Does the UVR time delay units include the undervoltage trip device?

Product Line:
Powerpact H, J, L, M, P and R frame molded case circuit breakers

Environment:
Products sold and used in the United States

Cause:
Need time delay for UVR - want to know if just time delay is needed, or time delay + undervoltage trip

Resolution:
The time delay units for Powerpact molded case circuit breakers, both adjustable and non-adjustable, do NOT include the undervoltage trip. Select the UVR separately to meet required control voltage for the circuit.

NOTE: For Powerpact H, J, L - Selecting the correct UVR when a Time Delay Unit is required
The output of the Time Delay Unit contains a large DC component, even when applied on an AC system.
This requires selecting a DC-rated UVR in lieu of an AC-rated UVR. Select as shown below

Table

Schneider Electric New Zealand

Explore more
Category:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Category:
  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings