How long must the signal be applied to the shunt trip on a Masterpact NW breaker?
Issue:
How long must the signal be applied to the shunt trip and shunt close on a Masterpact NW breaker to ensure proper operation?

Product Line:
Circuit Breakers

Resolution:
The breaker requires a shunt trip energization time of 200 ms to ensure that the breaker trip mechanism has completed its cycle and has returned to its starting point. A shorter signal will open or close the breaker, but has the risk of causing the mechanism to hang up and not close with the next close signal. It would close with a second signal however. To prevent operating problems, do not pass the signal through an aux contact (which will open in less than 50 ms). If a PLC is used, ensure the signal duration is 200 ms or more.

Schneider Electric New Zealand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings