TeSys T LTMR..EBD doesn't respond to network commands
Issue:
Tesys T does not respond to command via Ethernet. IP address can be pinged, registers can be read, and Tesys is configured for network control but will not respond to network commands.

Product Line:
LTMR Tesys T motor controllers.

Environment:
Products sold in the US

Cause:
Tesys was in configuration mode, not run mode.

Resolution:
The Tesys will not run in configuration mode. In run mode you only have command menu under the device tab in the latest DTM Library. Ensure you have the latest DTM Library Installed. This will allow you to place Tesys in Run mode and verify proper operation.

Schneider Electric New Zealand

Explore more
Product:
Range:
Category:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
Range:
Category:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings