CBGS-1
GIS MV primary cubicle up to 36kV
Discontinued
Overview
Features
Each functional unit consists of separate compartments:
. LV cabinet. Busbar compartment
. Main compartment (SF6 insulated)
. MV cable compartment
Performances :
. Technology:SF6. Standard:IEC
. Rated voltage:36kV
. Busbar system:Single / Double
. Rated current busbar:2500A
. Rated operational current:2000A
. Rated peak withstand current:31.5kA
. Internal Arc Classification:AFLR 25kA/1s
. Loss of service continuity:NA
. Partition class:NA
Benefits
Maximum safety in a reduced place
- Continuity of service:unaffected by the environment, double busbar option, sealed-for-life compartments, reduced gas pressure
- Maximum safety:operating safety (interlocks), IAC tested
- Investment optimization:space savings, maintenance savings...
Applications
- Indoor substation (HV/MV-MV/MV) for Power Supply Utilities, Windfarms, Airports, Traction substations, Large Industries...